Model 60 ENT
air handling unit with Enthalpy exchanger
Model 60 ENT is designed as a flexible, space-saving solution. Its narrow width of just 558 mm allows installation inside a cabinet. The 450 mm height provides sufficient space for installing a laundry tower beneath it. In addition, the innovative door mechanism enables the unit to be installed in a sliding-door cabinet. Model 60 ENT is suitable for a wide range of project types: terraced houses, apartment buildings, and single-family homes.
Airfi Enthalpy recovers both heat and moisture ensuring optimal indoor comfort, balanced humidity and reduced energy costs.
- Equipped with an ERV (energy recovery ventilation) core. Additional heating via an electric post-heater is used only when necessary.
- The AFPS™ defrost system ensures continuous ventilation and optimizes the unit’s performance in all conditions.
- Highest quality of filtration. Supply: ISO Coarse 90% + ePM1 55%, exhaust: ISO ePM10 60%
- Compatible with various building automation systems.
- Effortless installation thanks to the Click ceiling mounting frame. Wall installation is also possible.
Apartment size max.: 200 m²
Supply air: 356 m³/h
Extract air: 385 m³/h
Models
| Product code | Information | |
|---|---|---|
| Model 60 ENT (R) Electric | 11060011 | Enhalpy Exchanger |
| Model 60 ENT (L) Electric | 11060021 | Enhalpy Exchanger |
Contact Our Sales Team
Contact us- Dimensions (width x hight x depth)558 x 450 x 558
- Weight40 kg
- Duct outlets4 x 160, 1 x 125
- Kitchen bypassOn
- Condensate fittingCentre 66 mm from rear edge
- Condensate water trayTilted
- Max. extract air flow rate (100 Pa)385 m³/h
- Max. supply air flow rate (100 Pa)356 m³/h
- Specific energy consumption (SEC) in a cold climateA+
- Specific energy consumption (SEC) in an average climateA
- Extract air heat recovery annual efficiency classA+/A (kitchen bypass in use)
- Air handling unit’s specific electrical power class at rated air flowA
- Electricity230 V, 50 Hz, 10 A, max. 1165 W: Wall plug
- Post heater920 W (electric)
- Heat recovery typeEnthalpy Metalpic
Why choose Airfi Enthalpy Air Handling Unit
Air handling units with energy recovery
ventilation technology (ERV)
Model 53 mini ENT
Maximum apartment size: 160 m²
Supply air: 324 m³/h
Extract air: 342 m³/h
Model 60 ENT
Apartment size max. 200 m²
Supply air: 356 m³/h
Extract air: 385 m³/h
Model 130 ENT
Apartment size max: 250 m²
Supply air: 450 m³/h
Extract air: 511 m³/h
Model 150 ENT
Apartment size max.: 300 m²
Supply air: 572 m³/h
Extract air: 648 m³/h
Model 250 ENT
Apartment max size: 450 m²
Supply air: electric 893 / water 875 m³/h
Extract air: 954 m³/h (electric, water)
Model 350 ENT
Apartment size max: 550 m²
Supply air: electric 1256 / water 1242 m³/h
Extract air: 1325 m³/h (electric, water)